Types of Alarms - viewLinc 5.1

Vaisala viewLinc Enterprise Server version 5.1 User Guide

Document code
M212315EN
Revision
C
Language
English
Product
viewLinc 5.1
Content type
Product description
Product description > Features
Reference information
Document type
User guide

Alarms indicate issues that may require immediate resolution, provide notification about interruptions in communication between devices or hosts and the viewLinc Enterprise Server, updates about system status or configuration changes, and reminders about upcoming maintenance requirements.

Alarms are viewable in the Alarms window (device and system alarms and threshold alarms for Locations you have permission to view), the Sites window (device and threshold alarms for the Locations you have permission to view), or in the Overview window (device and threshold alarms for the Locations assigned to your views).

All alarm events are recorded in the event log, to ensure a secure audit trail.

Table 1. Alarm Descriptions
Alarm Type Description
System Event log validation alarms indicate whether changes have been made to the event log from outside the viewLinc system.
Database validation alarms indicate database corruption or configuration changes made to the historical database originating outside viewLinc.
System alarm settings are configured in System Preferences.
Threshold Threshold alarms indicate excessive condition changes in a monitored environment.
Threshold alarm settings are defined in threshold alarm templates and are then applied to Locations.
Device Device configuration alarms indicate interruptions collecting device data.
Host configuration alarms indicate synchronization errors between a device host or access point and the viewLinc Enterprise Server.
Device validation alarms indicate corruption in the device memory.
Device calibration alarms indicate upcoming calibration service requirements.
Host communication alarms occur when a device host or access point loses connection with the viewLinc Enterprise Server.
Device communication alarms indicate a communication error between a host computer, access point or viewLinc Enterprise Server, and its connected devices.
Device alarm settings are defined in templates.