Adding 300 Series Transmitters - viewLinc 5.1

Vaisala viewLinc Enterprise Server version 5.1 User Guide

Document code
M212315EN
Revision
C
Language
English
Product
viewLinc 5.1
Content type
Product description
Product description > Features
Reference information
Document type
User guide

Manage Devices

  1. Ensure no other users are logged on to the transmitter you want to add (from a command prompt on the connected PC, type telnet <IP address>).
  2. In Sites Manager select the Hosts and Devices tab.
  3. On the Hosts and Devices tree, select the Vaisala viewLinc Enterprise Server or a device host, then select Configure > Add Device.
  4. In the Add Device window, in the Device Class list, select 300 Series Transmitter.
  5. Complete the following:
    Timeout
    To ensure continuous monitoring, do not change (default 30 seconds).
    Connection Type
    If the transmitter has a LAN or WLAN module, select Network. If you use an external single or multi-port Ethernet device, choose COM Port.
    IP Address
    Type the IP address.
    Sample Rate
    Choose 90 (recommended, but you can modify the rate if you need more or less recorded data).
  6. Select Save.