Modbus communication - HMP110 - HMP113 - HMP60 - HMP63

HMP60 and HMP110 Series User Guide

Document code
M211060EN
Revision
L
Language
English
Product
HMP110
HMP113
HMP60
HMP63
Document type
User guide

The Modbus variant used in HMP60 and HMP110 series probes is Modbus RTU. Modbus support was added to HMP60 and HMP110 probes in 2016 for probe software version 2.1.4. The following table lists the default communication settings used when Modbus is enabled at the factory (chosen when ordering).

Table 1. Default Modbus communication settings
Description Default value
Serial bit rate 19200
Parity None
Number of data bits 8
Number of stop bits 2
Flow control None
Modbus device address 240
Serial delay 0
Communication mode Modbus RTU

Use Vaisala Insight software to change the Modbus serial communication settings if needed. Download Vaisala Insight software at www.vaisala.com/insight.

The instrument must be switched off and on before the communication setting changes take effect.