Register number | Register address | Register description | Data format | Unit / Valid range |
---|---|---|---|---|
Filtering | ||||
785 | 0310hex | Measurement filtering factor | 32-bit float | 0.001 (maximum filtering) … 1.000 (no filtering) |
0311hex | ||||
Communication | ||||
1537 | 0600hex | Modbus address | 16-bit integer | 1 … 247 |
1538 | 0601hex | Bit rate 1 | 16-bit integer |
5 = 9600 6 = 19200 7 = 38400 8 = 57600 |
1539 | 0602hex | Parity, data, stop bits 1 | 16-bit integer |
0 = None, 8, 1 1 = None, 8, 2 2 = Even, 8, 1 3 = Even, 8, 2 4 = Odd, 8, 1 5 = Odd, 8, 2 |
1540 | 0603hex | Response delay | 16-bit integer |
0 … 1020 ms |
1541 | 0604hex | Protocol | 16-bit integer |
6 = Modbus RTU |
1542 | 0605hex | Restart device | 16-bit integer |
When writing to register: 1 = Restart the device |
If incompatible settings/protocol are selected and the probe is then restarted, it might no longer be possible to communicate with the probe using Modbus. You can override invalid communication settings in Vaisala Insight software, Settings menu. See Vaisala Insight software. |
1 Changed setting will be activated on device restart.