Before you connect an HMP60 or HMP110 series probe to a device, it is recommended to power off the device. |
For a secure connection to the probe, connect to the 4-pin M8 connector using a threaded connector.
Pin-out of HMP60 / HMP63 / HMP110 analog / HMP113 / HMP110T
- 1
-
5 ... 28 VDC (Vout 0 ... 1 / 0 ... 2.5 V)
8 ... 28 VDC (Vout 0 ... 5 / 1 ... 5 V)
Wire color: brown
- 2
-
Channel 1: RH / Td / T
0 ... 1 / 2.5 / 5 V, 1 ... 5 V
Wire color: white
- 3
-
GND / AGND
Wire color: blue
- 4
-
Channel 2: RH / Td / T
0 ... 1 / 2.5 / 5 V, 1 ... 5 V
(HMP110T has no output on channel 2)
Wire color: black
Pin-out of HMP110REF / HMP110 digital
- 1
-
5 ... 28 VDC
Wire color: brown
- 2
-
RS-485: - / B
Wire color: white
- 3
-
GND
Wire color: blue
- 4
-
RS-485: + / A
Wire color: black
Probe | Grounding method |
---|---|
HMP63 HMP113 |
Vaisala recommends to use a shielded cable and connect the shield to ground. In the shielded cables supplied by Vaisala, the threaded connector connects the shield to the probe housing. |
HMP60 HMP110 HMP110T HMP110REF |
There are two ways to ground the probe depending on installation type. Choose only one of these methods:
|
When the probe is connected to a power supply, there is a delay as the probe starts up and the analog output stabilizes. The delay
depends on the output type, and on the operating voltage that is supplied to the probe:
|