HMP113 specifications - HMP110 - HMP113 - HMP60 - HMP63

HMP60 and HMP110 Series User Guide

Document code
M211060EN
Revision
L
Language
English
Product
HMP110
HMP113
HMP60
HMP63
Document type
User guide
Table 1. HMP113 measurement performance
Property Description/Value
Relative humidity
Measurement range 0 … 100 %RH
Accuracy (incl. non-linearity, hysteresis, and repeatability):

at 0 … +40 °C (+32 … +104 °F)

±1.5 %RH (0 … 90 %RH)

±2.5 %RH (90 … 100 %RH)

at −40 … 0 °C (−40 … +32 °F) and +40 … +60 °C (+104 … +140 °F)

±3.0 %RH (0 … 90 %RH)

±4.0 %RH (90 … 100 %RH)

Factory calibration uncertainty at +20 °C (+68 °F):

±1.1 %RH (0 … 90 %RH)

±1.8 %RH (90 … 100 %RH)

Humidity sensor HUMICAP® 180R
Stability ±2 %RH over 2 years
Temperature
Measurement range −40 … +60 °C (−40 … +140 °F)
Accuracy:
at 0 … +40 °C (+32 … +104 °F) ±0.2 °C (±0.36 °F)
at −40 … 0 °C (−40 … +32 °F) and +40 … +60 °C (+104 … +140 °F) ±0.4 °C (±0.72 °F)
Temperature sensor Pt1000 RTD Class F0.1 IEC 60751
Dew point temperature
Measurement range −40 … +60 °C (−40 … +140 °F)
Accuracy (incl. non-linearity, hysteresis, and repeatability):

at 0 … +40 °C (+32 … +104 °F)

when dew point depression < +15 °C (+59 °F) 1

when dew point depression +15 … +25 °C (+59 … +77 °F)

 

±1 °C (±1.8 °F)

±2 °C (±3.6 °F)

at −40 … 0 °C (−40 … +32 °F) and +40 … +60 °C (+104 … +140 °F), when dew point depression < +15 °C (+59 °F)

±2 °C (±3.6 °F)

Analog outputs
Accuracy at +20 °C (+68 °F) ±0.2 % of FS
Temperature dependence ±0.01 % of FS/°C (±0.006 % of FS/°F)
Table 2. HMP113 calculated parameters
Property Description/Value
Measurement ranges
Dew point temperature −40 … +60 °C (−40 … +140 °F)
Wet bulb temperature −40 … +60 °C (−40 … +140 °F)
Absolute humidity 0 … 130 g/m3 (0 … 57 gr/ft3)
Mixing ratio 0 … 153 g/kg (0 … 1069 gr/lb)
Enthalpy −40 … 459 kJ/kg (−9.6 … 207 BTU/lb)
Table 3. HMP113 operating environment
Property Description/Value
Operating temperature −40 … +60 °C (−40 … +140 °F)
EMC compliance EN 61326-1, basic immunity test requirements
Table 4. HMP113 inputs and outputs
Property Description/Value
Power consumption 1 mA average, max. peak 5 mA
Operating voltage 2
With 1 V / 2.5 V output 5 … 28 VDC
With 5 V output 8 … 28 VDC
With loop power converter 8 … 28 VDC
With digital output 5 … 28 VDC
Start-up time
Probes with analog output

4 s at operating voltage 13.5 … 16.5 VDC

2 s at other valid operating voltages

Probes with digital output 1 s
Outputs
2 channels 0 … 1 VDC / 0 … 2.5 VDC / 0 … 5 VDC / 1 … 5 VDC
1-channel loop-power converter (separate module, compatible with humidity accuracy only) 4 … 20 mA
Digital output (optional) RS-485 2-wire half duplex, supports Modbus RTU
External loads
0 … 1 V RL min 10 kΩ
0 … 2.5 V /0 … 5 V RL min 50 kΩ
Output parameters
Relative humidity, temperature, dew point temperature, wet bulb temperature, absolute humidity, mixing ratio, enthalpy
Table 5. HMP113 mechanical specifications
Property Description/Value
IP rating IP54 3
Cable connector 4-pin M8 (IEC 60947-5-2)
Materials
Body PC/ABS blend
Grid filter PC (glass reinforced)
Cable Polyurethane or FEP
Weight
Probe 9 g (0.3 oz)
Probe with 0.3 m (1 ft) cable 20 (0.7 oz)
1 Dew point depression = ambient temperature − dew point
2 Use lowest available operating voltage to minimize heating.
3 Not applicable with the plastic grid filter.