The limit alarm is activated when the measured parameter goes below the low limit or above the high limit. The alarm can be specified during ordering for a specified parameter, or configured on the serial line using the ALARM command.
When ordering a limit alarm, the alarm levels are set as follows:
- For current output, an active alarm is indicated by the current being at the maximum of the scale (20 mA).
- For voltage output, an active alarm is indicated by the voltage being at the maximum of the selected scale. For example, if the voltage output scale is 0 … 5 V, an output of 5 V indicates the alarm is active.
Syntax | Description |
---|---|
ALARM ?<cr> | View the current alarm settings. |
ALARM<cr> | Select at the prompt (?) whether the alarm is enabled or disabled and define the alarm limits. |
The following example shows that a high limit alarm has been enabled for channel 1. If the measured value rises above the -40.00 °C Td limit, analog channel 1 is set to 5 V (Limit Hi = -40.00, Level Hi = 5.00). The malfunction alarm (aerr) is disabled for both channels. Note that the term quantity in the serial interface corresponds to measurement parameter.
|
Avoid enabling more than one alarm type for a channel. |