To minimize the output noise:
- Wire only the analog outputs (V/mA) to Port I
- Connect the power supply only to Port II
| Avoid connecting the Port I and Port II grounds (pin #3) together |
The wiring of pinouts 1 … 4 in ports I and II in the output minimization option is described in the following table.
Table 1. Output noise minimization wiring option pinouts and wire colors
Pin |
Connector I |
Connector II |
Wire color |
1 |
Not wired |
VDC supply+ |
Brown |
2 |
Signal Ch 1+ |
RS-485 - / B |
White |
3 |
GND |
GND |
Blue |
4 |
Signal Ch 2+ / LED |
RS-485 + / A |
Black |