For item codes, see Spare parts and accessories. |
You can install only one type of device or measurement point (PDT101 transmitters, analog input channels, safety barriers, or galvanic isolators) per row in the cabinet. |
In cabinet models with 5 to 8 data loggers, you need 2 serial port servers. One serial port server controls the traffic of maximum 4 data loggers. |
Make sure to number the data loggers as well as the cable sets and wires in the Analog Wiring Set before you install and connect them. |
DL4000 data loggers are delivered with default factory settings. This applies both to the factory-installed data loggers and the ones delivered as spare parts. For instructions on configuring measurement units and scaling in the data loggers, see the Vaisala viewLinc Enterprise Server User Guide for your viewLinc version, available at www.vaisala.com/viewlinc. |
Follow the steps below to install terminal blocks for analog input channels as new devices to an empty DIN rail in CAB100B.
You can apply this installation procedure also when expanding the number of analog input channels in the cabinet. For example, to increase the number of analog input channels on a DIN rail from 4 to 12, order 2 Analog Wiring Sets and 2 data loggers.
Refer to CAB100B layout diagrams when planning the installation.