Adding analog input channels to CAB100B - CAB100

CAB100 Installation Guide

Document code
M212242EN
Revision
D
Language
English
Product
CAB100
Document type
User guide
  • Empty DIN rail in the cabinet 1
  • Analog Wiring Set (Vaisala item code: ASM213078SP). 2 One set contains the following:
    • Cable set, 24 V DC power block to analog terminal block
    • Cable set, data logger to analog terminal block
    • Data logger data cable
    • Data logger holder
    • Terminal block accessories for 4 analog input channels
    • Document Vaisala CAB100 Assembling Analog Channel Terminal Block Technical Note (M212262EN)
  • DL4000 data logger(s), 1 logger per 4 analog input channels
  • Small flat head screwdriver

For item codes, see Spare parts and accessories.

You can install only one type of device or measurement point (PDT101 transmitters, analog input channels, safety barriers, or galvanic isolators) per row in the cabinet.

In cabinet models with 5 to 8 data loggers, you need 2 serial port servers.

One serial port server controls the traffic of maximum 4 data loggers.

Make sure to number the data loggers as well as the cable sets and wires in the Analog Wiring Set before you install and connect them.
DL4000 data loggers are delivered with default factory settings. This applies both to the factory-installed data loggers and the ones delivered as spare parts. For instructions on configuring measurement units and scaling in the data loggers, see the Vaisala viewLinc Enterprise Server User Guide for your viewLinc version, available at www.vaisala.com/viewlinc.

Follow the steps below to install terminal blocks for analog input channels as new devices to an empty DIN rail in CAB100B.

You can apply this installation procedure also when expanding the number of analog input channels in the cabinet. For example, to increase the number of analog input channels on a DIN rail from 4 to 12, order 2 Analog Wiring Sets and 2 data loggers.

Refer to CAB100B layout diagrams when planning the installation.

  1. De-energize the cabinet:
    1. Switch off mains power and the circuit breaker located inside the cabinet.
      1
      Circuit breaker
    2. Only when expanding the analog terminal block installation on a DIN rail:
      Disconnect the analog channel 24 V DC power cable connector from the power block, located on the right-hand side of the cabinet.
  2. Remove the cable duct cover below the empty DIN rail reserved for the analog terminal block.

    Remove also the long vertical cable duct cover in the middle of the cabinet.

  3. Assemble the new analog channel terminal block.

    See the instructions in Vaisala CAB100 Assembling Analog Channel Terminal Block Technical Note (M212262EN), included in the Analog Wiring Set (ASM213078SP).

  4. Mount the analog channel terminal block on the DIN rail.
  5. Assemble the data logger holder.
    1. Place the data logger in the logger holder.
    2. Fit the cover into place.
    3. Tighten the screw by hand.
  6. Connect the logger data cable to the RS-232 serial port in the data logger.

    Use a small flat head screwdriver to tighten the screw attached to the connector.

  7. Mount the data logger on the DIN rail, preferably at the right-hand end of the rail.

    Rest the logger holder locking mechanism on the DIN rail and push down firmly. This will click the device into place.

  8. Connect the logger data cable to a free port in the serial port server.
  9. Connect the analog channel terminal block to the data logger and to the 24 V DC power block, as shown in 10 to 12 below.

    Use the cables in the Analog Wiring Set (Vaisala item code: ASM213078SP).

    1
    Cable set for connecting data logger to analog terminal block
    2
    Cable set for connecting 24 V DC power block to analog terminal block
  10. Connect the cable sets to the analog channel terminal block.
    1
    Logger to analog cable set
    2
    Power cable set
  11. Connect the black terminal connector of the logger to analog cable set to the DL4000 data logger.
  12. Connect the power cable set to the power block located on the right-hand side of the cabinet.
    1
    Vertical cable duct
    2
    Power cable set connected to power block
  13. Route the wires along the cable ducts.
  14. The new analog channel terminal blocks are now mounted and connected.
    1
    Logger to analog cable set connected to analog channel terminal block
    2
    Power cable set connected to analog channel terminal block
    3
    Power cable set connected to power block
    4
    Logger to analog cable set connected to data logger
  15. Insert any extra length of wire into the cable ducts and replace the cable duct covers.
  16. Only when expanding the analog terminal block installation on a DIN rail:

    Reconnect the 24 V DC power cable connector (disconnected in 1.b) in the power block.

  17. Reconnect power in the cabinet.
    1. Switch on the circuit breaker.
    2. Switch on mains power.
1 Required only when introducing analog input channels as new devices in CAB100B.
2 You need 3 Analog Wiring Sets (Vaisala item code: ASM213078SP) to assemble a 12-channel terminal block.