For item codes, see Spare parts and accessories. |
The partition plate is needed for isolating the intrinsically safe area from the non-intrinsically safe area inside the cabinet. |
Each set of 4 galvanic isolators requires a Galvanic Isolator Wiring Set and a data logger of its own. |
You can install only one type of device or measurement point (PDT101 transmitters, analog input channels, safety barriers, or galvanic isolators) per row in the cabinet. |
In cabinet models with 5 to 8 data loggers, you need 2 serial port servers. One serial port server controls the traffic of maximum 4 data loggers. |
Make sure to number the data loggers as well as the cable sets and wires in the Galvanic Isolator Wiring Set before you install and connect them. |
Follow the steps below to add new galvanic isolators to an existing set of devices in CAB100B. Refer to CAB100B layout diagrams when planning the installation.
For instructions on introducing galvanic isolators as new devices to an empty DIN rail in the cabinet, see Adding galvanic isolators as new modules to CAB100B.
The Galvanic Isolator Wiring Set consist of wiring for 4 devices. Any unused wires in the Wiring Set have been placed in the cable duct at the factory. If you have, for example, 3 isolators installed on a DIN rail, and want to complete the set by installing a fourth one, use the existing isolator wires present in the cable duct.