When you choose the installation location for the probe, consider the following:

  • Verify the operating environment specification of the probe model. The probe head typically has a much wider operating temperature range than the probe body.
  • If the temperature of the measured environment differs greatly from ambient temperature, the entire probe head and preferably plenty of cable must be inside the measured environment. This prevents measurement inaccuracy caused by heat conduction along the cable.
  • Probe mounting options are model-specific.
Figure 1. Example installation
1

Mount the probe head horizontally to prevent any water condensing on the probe head from running to the sensors.

2
Let the cable hang loosely to prevent condensed water from running along the cable to the probe body or probe head.
3
Attach the probe body to a wall or other surface using supplied probe holder (item code ASM213582).
4
Cable to Modbus master or Indigo device.