Calibration and adjustment with Insight PC Software - HMD60 - HMD62 - SWINSIGHT10 - TMD60 - TMD62

HMD62 TMD62 User Guide

Document code
M212016EN
Revision
D
Language
English
Product
HMD60
HMD62
TMD60
TMD62
Document type
User guide
Figure 1. Insight calibration view (HMD62 example)
You can use the Insight PC software to calibrate and adjust the RH or T measurement in 1 or 2 points. Either a reference environment (such as a humidity calibrator) or a reference instrument (for example, a second HMD60 transmitter) can be used when adjusting.
CAUTION When you use the Insight PC software to adjust the measurement or to restore the factory settings, always return the physical adjustment trimmer(s) on the transmitter component board to the middle position before starting. When you make an adjustment with Insight, the position in which the adjustment trimmer is at that point is set as the ±0 point.