Calibration and adjustment overview - HMD60 - HMD62 - TMD60 - TMD62

HMD62 TMD62 User Guide

Document code
M212016EN
Revision
D
Language
English
Product
HMD60
HMD62
TMD60
TMD62
Document type
User guide
You can calibrate or adjust the transmitter's measurement output using one of the following options:
  • 1-point adjustment with the RH and T trimmers on the HMD60 component board (adjustment range: -5 %RH … +5 %RH and -0.3 °C … +0.3 °C (-0.54 °F … +0.54 °F).
  • 1-point or 2-point adjustment by connecting the transmitter to Vaisala Insight PC software (requires USB cable 219690).
  • 1-point adjustment by connecting the transmitter to an MI70 handheld indicator (requires MI70 connection cable 219980SP).