Available parameters and default scaling - HMD60 - HMD62 - TMD60 - TMD62

HMD62 TMD62 User Guide

Document code
M212016EN
Revision
D
Language
English
Product
HMD60
HMD62
TMD60
TMD62
Document type
User guide

HMD62 measurement parameters and default analog output scaling

Table 1 shows the available output parameters and the default analog output scaling of the parameters for HMD62.

Table 1. HMD62 measurement parameters and default scaling
Parameter Default scaling for 4 … 20 mA output range
Relative humidity (RH) 0 … 100 %RH
Temperature (T) -20 ... +80 °C (-4 ... +176 °F)
Dew point temperature (Td) -40 ... +80 °C (-40 ... +176 °F)
Dew point/frost point temperature (Tdf) -40 ... +80 °C (-40 ... +176 °F)
Absolute humidity (A) 0 … 300 g/m3 (0 … 131.1 gr/ft3)
Mixing ratio (X) 0 … 600 g/kg (0 … 4200 gr/lb)
Wet-bulb temperature (Tw) -40 ... +80 °C (-40 ... +176 °F)
Enthalpy (H) -40 … 1600 kJ/kg (-9.5 ... 695.6 Btu/lb)

TMD62 measurement parameters and default analog scaling

Table 2 shows the available output parameters and the default analog output scaling of the parameters for TMD62.

Table 2. TMD62 measurement parameters and default scaling
Parameter Default scaling for 4 … 20 mA output range
Temperature (T) -20 ... +80 °C (-4 ... +176 °F)

Changing measurement parameter scaling

If your application requires an analog output scaling that differs from the defaults shown in Table 1 and Table 2, you can configure the scaling by connecting the transmitter to Vaisala Insight PC software (requires Vaisala USB cable 219690).