Configuration registers - HMD110 - HMD112 - HMS110 - HMS112 - HMW110 - HMW112 - TMD110 - TMI110 - TMW110

HMDW110 with TMI110 User Guide

Document code
M211726EN
Revision
F
Language
English
Product
HMD110
HMD112
HMS110
HMS112
HMW110
HMW112
TMD110
TMI110
TMW110
Document type
User guide
Table 1. Modbus configuration data registers (writable)
Register number (decimal) Address (hexadecimal) Register description Data format Unit / valid range
Filtering
785 0310hex Filtering factor 32-bit float 0.001 (maximum filtering) ... 1.000 (no filtering)
Communication
1537 0600hex Modbus address 16-bit integer 1 ... 247
1538 0601hex Bit rate (b/s) 1 16-bit integer

5 = 9600

6 = 19200

7 = 38400

8 = 57600

1539 0602hex Parity, data, stop bits 1 16-bit integer

0 = N81

1 = N82

2 = E81

3 = E82

4 = O81

5 = O82

1540 0603hex Response delay 16-bit integer 0 ... 1020 ms
1541 0604hex Protocol 16-bit integer

6 = Modbus RTU

Functions
1542 0605hex Restart device 16-bit integer Write 1 to restart device
1 Changed setting will be activated on device restart.