OPT100 cable glands and connectors - OPT100

OPT100 Installation Guide

Document code
M211857EN
Revision
V
Language
English
Product
OPT100
Document type
User guide
Figure 1. Cable glands and connectors on OPT100 cabinet
# Label Description Cable/pipe diameter Tool size Tightening torque
1 Oil Out Oil return to transformer. 10 mm (0.39 in) 19 mm -
2 Oil In Oil intake from transformer. 10 mm (0.39 in) 19 mm -
3 Ground connection. 1.5–50 mm2 (16–1/0 AWG) conductor 5 mm

3.5 Nm

(1.5–10 mm2)

10 Nm

(15–50 mm2)
4 RS-485 RS-485 connection. 5–10 mm (0.20–0.39 in) 20 mm 5 Nm
5 Relay control out Relay control to OPTPSU. Use Vaisala cable CBL210539. 7–12 mm (0.28–0.47 in) 24 mm 10 Nm
6 DC in DC input from OPTPSU. Use Vaisala cable CBL210544. 9–16 mm (0.35–0.63 in) 30 mm 12 Nm
7 Ethernet Ethernet connection. Use shielded outdoor Ethernet cable. Assemble the included protection shell on the RJ45 connector. - - -
8 Spare Not reserved. 5–10 mm (0.20–0.39 in) 20 mm 5 Nm
9 Spare Not reserved. 7–12 mm (0.28–0.47 in) 24 mm 10 Nm