RS-485 termination and biasing - OPT100

OPT100 Installation Guide

Document code
M211857EN
Revision
V
Language
English
Product
OPT100
Document type
User guide
Figure 1. Location of the RS-485 repeater inside the DGA monitor cabinet.

Use of termination and bias resistors on the RS-485 line is configured using DIP switches on the isolated RS-485 repeater. Change their configuration if necessary for your system. See Table 1.

There are two banks of DIP switches on the underside of the RS-485 repeater. Switches for configuring the RS-485 output are at the front of the repeater, next to the grounding terminal (green screw).

Figure 2. Location of DIP switches on the RS-485 repeater
1
DIP switches for configuring the RS-485 output.
2
DIP switches for configuring the internal serial connection. Do not change the settings of this bank.
Table 1. DIP switch configuration of RS-485 output
Switch number Result
Switch 1 Switch 2 Switch 3 Switch 4 Communication mode
ON ON ON ON RS-485 2-wire half-duplex (default)
ON OFF OFF OFF RS-485 4-wire full-duplex
OFF OFF OFF OFF RS-422 full-duplex
Switch 5 Termination resistor
ON Use built-in 120 Ω termination
OFF Use external or no termination (default)
Switch 6 Transmit bias resistor
ON Use external or no bias resistor
OFF Use built-in 1.2 kΩ transmit bias resistor (default)
Switch 7 Receive bias resistor
ON Use external or no bias resistor (default)
OFF Use built-in 1.2 kΩ receive bias resistor

Switch 8 is not used.

CAUTION DGA monitor is wired for 2-wire communication so do not change the communication mode.