Setting relay activation limit without hysteresis - INDIGO200SERIES - INDIGO202

Indigo202 User Guide

Document code
M212843EN
Revision
B
Language
English
Product
INDIGO200SERIES
INDIGO202
Content type
Product description
Product description > Features
Product description > Functions
Document type
User guide

You can set the relay to activate when the probe measurement exceeds or falls below a set limit. When you configure a single setpoint for relay activation without hysteresis, the relay switches on or off immediately when the measurement moves over or below the setpoint.

Figure 1. Relay settings example: one setpoint without hysteresis
To define a single setpoint for relay activation when the measurement exceeds the defined activation limit (Activate above) without using hysteresis:
  1. Select to access Insight main menu.
  2. In the Configure Device menu, select either relay A or relay B.
  3. Enable the relay output by setting Relay output on/off to ON.
  4. Select the measurement parameter that is used to control the relay with the Output parameter dropdown.
    The parameter options depend on the connected probe. Note that the parameter units are defined in the Settings menu: see Unit settings.
  5. Enter the activation limit value in the Activate above field.
    With this configuration, there is no hysteresis buffer. The relay activates or switches off immediately after passing this point.
  6. Leave the Activate below field empty and set the Hysteresis field value as 0 (no hysteresis).
  7. Select the Error output state for the relay.
  8. Select Save to store the configuration.