Figure 1. Calibration menu main view example
(CO2 probe)
The Calibrate menu in Insight PC software contains options for calibrating and adjusting the measurement
of the probe you have connected to the transmitter. You can also view the current adjustment
and restore the probe's factory adjustments.
The range of available options (for
example, environmental compensations and the number of adjustment points) varies depending
on the features of the connected probe.
The menu examples presented here are
examples of calibration options that are available when a CO2 probe is connected
to the transmitter.
CAUTION Before adjusting a probe's
measurement, make sure that you have familiarized yourself with the probe-specific
calibration requirements such as possible adjustment limits and environmental compensation
interdependencies. See the user documentation of the probe for probe-specific information.
Starting calibration
To open the calibration menu, select to access
Insight main menu. In the main menu, select Calibrate. Figure 2. Calibration menu selection
Restoring factory adjustment
Before adjusting the probe measurement, remove any possible earlier adjustments with the
Restore factory adjustment selection.Figure 3. Restore factory adjustment selection
Always restore factory
adjustment before entering a new adjustment. This prevents any possible earlier
adjustments having an effect on the new adjustment you make.