Exception responses - DMP5 - DMP6 - DMP7 - DMP8 - DMPX

DMP Series User Guide

Document code
M212357EN
Revision
E
Language
English
Product
DMP5
DMP6
DMP7
DMP8
DMPX
Document type
User guide
Table 1. Modbus exception responses
Code Name Reason
01 ILLEGAL FUNCTION Unsupported function code
02 ILLEGAL DATA ADDRESS Register address or Object ID out of valid ranges
03 ILLEGAL DATA VALUE Otherwise invalid request

Accessing unavailable (temporarily missing) measurement data does not generate a Modbus exception. “Unavailable” value (a quiet NaN for floating point data or 0x8000 for integer data) is returned instead. An exception is generated only for any access outside the applicable register ranges.