Adding particle counter as viewLinc Modbus device - viewLinc 5.1

Climet CI-3100 Modbus viewLinc system Integration Guide

Document code
M212824EN
Revision
A
Language
English
Product
viewLinc 5.1
Document type
Technical note
  1. In Sites Manager select the Hosts and Devices tab.
  2. In the Hosts and Devices tree, select add Non-Vaisala Modbus Device from the Configure drop-down menu.
  3. Fill out the Device Information in the Communication Settings fields:
    • IP Address = IP Address of the particle counter
    • Port Number = 502
    • Unit ID = 20 (other values can be entered, as shown below)
  4. Add viewLinc channel details.
    For the initial configuration and verification step use the scale factor of 1, even if you are performing metric conversions.
    Location naming scheme should be: <<Location Name>>_<<Measurement Type>>
    • Location name = unique description for the room, Biological Safety Cabinet (BSC) or location ID where the particle count is taking place.
    • Measurement type = 0.5µm, 5.0µm, or Flow
    Table 1. Default counts per cubic foot
    Description Measurement type Unit Register type Address Data Format Scale Offset
    <<Location Name>>_0.5µm Others C/CF Holding Register 0 32-bit Integer, Big-endian 1 0
    <<Location Name>>_5.0µm Others C/CF Holding Register 2 32-bit Integer, Big-endian 1 0
    <<Location Name>>_Flow Others %Flow Holding Register 18 32-bit Integer, Big-endian 1 0

     

  5. After adding each channel, click Refresh current value to get real-time values in Counts per Cubic Foot. These values should match the values displayed in the Climet Cl-3100 web user interface.
  6. To perform metric conversion, select the device you created above, then select Edit Properties from the Configure drop-down menu. Metric conversion scale factor: 1 cubic meter = 35.315 Cubic Feet.
    Table 2. Metric counts per cubic foot
    Description Measurement type Unit Register type Address Data format Scale Offset
    <<Location Name>>_0.5µm Others C/CM Holding Register 0 32-bit Integer, Big-endian 35.315 0
    <<Location Name>>_5.0µm Others C/CM Holding Register 2 32-bit Integer, Big-endian 35.315 0
    <<Location Name>>_Flow Others %Flow Holding Register 18 32-bit Integer, Big-endian 1 0

     

  7. Click Save.