Sensor status values - AWS310 - AWS310-SITE - AWS430 - MAWS201

AWS Client User Guide

Document code
M210932EN
Revision
F
Language
English
Product
AWS310
AWS310-SITE
AWS430
MAWS201
Document type
User guide
Table 1. Sensor status values
Value Description Interface
0 The sensor is working properly. Serial/Analog 1
1 Not measured yet. Serial/Analog
2 Interface not initialized. Serial
3 Communication time‑out occurred. Serial
4 Unknown data received. Serial
5 Communication is functioning, but the sensor reports errors. Use the sensor's own service interface to find out the cause. Serial
6 Sensor communication is paused because service connection to the sensor is open. Serial
7 Message sequence numbers are overlapping in the Autotrac satellite transceiver interface. Serial
8 … 19 Reserved. N/A
20 Excitation failure caused by an overload in the excitation output. Analog
21 Input voltage is out of range or the A/D conversion has failed due to an internal error. Analog
22 The sensor is disconnected or sensor cable is damaged. Analog
23 Sensor output exceeds the minimum or maximum limits. Analog
24 Change in sensor output exceeds the maximum step. Analog
25 Internal configuration error occurred. Analog
26 Error in reference measurement. Analog
27

Internal voltage error occurred or the QML data logger is damaged.

Analog

28 BARO-1 calibration data error. Analog
30 The measurement or the sensor has been manually disabled. Serial/Analog
99 Sensor status not supported. Serial/Analog
1 Analog includes also counter/frequency interfaces.