The data message that RSI51 sends to the AviMet system contains 4 main data items.

Table 1. Data items in RSI51 data message
Data item Value
Message header For example, 1A.
Runway light intensity setting
  • 32, 16, 8, 4, 2, or 1
  • 0 = No voltage signal, or voltage signal is below 12 VDC or above 48 VDC
Runway-in-use setting 1
  • 1 = Runway 1 is active
  • 0 = Runway 1 is inactive
Runway-in-use setting 2
  • 1 = Runway 2 is active
  • 0 = Runway 2 is inactive

You can use only one runway light intensity value and one of the runways-in-use at a time. If you use two or more runway light intensity values, the fail-safe activates and only the smallest value is displayed in the output. If both or neither of the runway-in-use values are active at the same time, the data message shows the values as‑is but the status bit message displays an alarm.

The activation of the runway light intensity setting depends on the voltage signal, which is first wired to the terminal block and then led to the analog input channel on the QML data logger. The terminal block has a voltage divider with 10 kΩ and 1 kΩ resistors, which allows the QML data logger to receive the signal. If there is no voltage signal or if the voltage signal is below 12 VDC or above 48 VDC, the runway light intensity and runway-in-use values are 0.

Table 2. Runway light intensity and runway-in-use output valuesThe following table shows the runway light intensity and runway-in-use values when a 12 … 48 VDC voltage signal goes through the terminal block.
QML data logger channel Terminal block Output value
Runway light intensity setting
CH0, H pin 5 32
CH0, L pin 6 16
CH1, H pin 7 8
CH1, L pin 8 4
CH2, H pin 9 2
CH2, L pin 10 1
Runway-in-use setting 1
CH3, H pin 11 1
Runway-in-use setting 2
CH3, L pin 12 1