Vaisala vNet PoE Data Logger Interface specifications - CAB100 - VNET

CAB100 Installation Guide

Document code
M212242EN
Revision
D
Language
English
Product
CAB100
Document type
User guide
Table 1. vNet operating environment
Property Description/Value
Operating temperature −25 … +70 °C (−13 … +158 °F)
Storage temperature −40 … +85 °C (−40 … +185 °F)
Operating humidity 0 … 90 %RH (non-condensing and not to exceed a mixing ratio of 38.5 g/kg)
Table 2. vNet inputs and outputs
Property Description/Value
Ethernet connectivity IEEE 802.3af (Class 1) 1, bandwidth 10Base-T
Connectivity cable

Category 5/5e

RJ-45 connector

1.83 m (6 ft)

Operating voltage 2

12 … 30 V DC

Plugs into vNet jack labeled 12 V

Output voltage

Model CDL-VNET-LPC

Nominal: 15 V DC

Maximum: 350 mW

Power consumption

Model CDL-VNET-LPC

Typical: 900 mW

Maximum: 1.35 W

Power supply 3
North America

12 V DC / 0.5 A max. out

120 V AC in

International

12 V DC / 1.66 A max. out

100 … 240 V AC in

Table 3. vNet mechanical specifications
Property Description/Value
Dimensions (H × W × L) 43 × 102 × 102 mm (1.7 × 4.0 × 4.0 in)
Weight 180 g (6.3 oz)
Table 4. vNet general specifications
Property Description/Value
Data logger compatibility

v6.00 hardware and higher

Includes models VL and SP 1000, 1700, 1200, 1016, 1416, 1400, 2000, 4000

LED indicators Link, activity, power, data logger communications
Device configuration

HTTP Web Interface

PC-based configuration wizard

viewLinc Aware Requires one vNet to be programmed with the viewLinc server IP address. Other vNets on the subnet will automatically self-configure.
Addressing

DHCP/RARP

ARP-Ping

Static IP for IP address assignment

Net BIOS name

Firmware Field upgradable firmware
Compliance
Emissions/Immunity

FCC Part 15 and CE

EN 50581:2012

EN 55032:2012/AC:2013 Class B

EN 61326-1:2013

Conformity

RoHs, 2011/65/EU

WEEE

1 Max. PSE power reservation is 4.00 W.
2 Optional for use without PoE.