Overview of Modbus data integration feature - AP10 - RFL100 - Jade Smart Cloud

Modbus Data Integration with Jade Smart Cloud and VaiNet Technical Note

Product status
Document code
M213335EN-A
ft:locale
en-US
Product
AP10
RFL100
Jade Smart Cloud
Document type
Technical note

Vaisala Jade Smart Cloud supports local data integration of data from VaiNet devices using Modbus TCP/IP protocol. Local data integration enables third‑party systems such as Building Management Systems (BMS) to access the latest measurement data and status information of VaiNet devices in the system through AP10 access points.

In a VaiNet system, data loggers can connect to any available access point within the same VaiNet segment. This enables redundant setups where each data logger is in the wireless signal range of at least 2 access points. To avoid the need to read data from every access point using separate Modbus requests, the Modbus data integration feature is implemented so that AP10 devices act as Modbus TCP/IP relays. Measurement and status data from VaiNet devices that have been assigned Modbus IDs can be read through a single AP10 device.

When data loggers switch access points, their measurement and status data will temporarily persist on the old access point. The relay logic handles these cases by only forwarding the data with the latest time stamp.