Requirements and limitations - AP10 - RFL100 - Jade Smart Cloud

Modbus Data Integration with Jade Smart Cloud and VaiNet Technical Note

Product status
Document code
M213335EN-A
ft:locale
en-US
Product
AP10
RFL100
Jade Smart Cloud
Document type
Technical note

Jade Smart Cloud add-on license is required

Modbus data integration is an add-on feature of Jade Smart Cloud. It must be enabled in the tenant that the VaiNet devices are associated with.

If VaiNet devices do not communicate with Jade Smart Cloud for 2 weeks, their Modbus communication stops working until they reconnect. During communication breaks shorter than 2 weeks, the Modbus communication works normally without interruption.

AP10 devices must have stable IP addresses

For Modbus data integration feature to work properly, the IP address of AP10 devices must not change. Since setting a static IP address is not supported on AP10 devices that are used with Jade Smart Cloud, you must configure the DHCP server to reserve a specific IP address for each AP10 based on their MAC address.

Networking limitations

Every AP10 device must be able to communicate directly over Ethernet with the other AP10 devices that share the same Modbus configuration. The simplest way to ensure this is to place them all in the same network subnet, and make sure TCP port 502 is not blocked by firewalls.

If AP10 devices of a Modbus configuration are in different subnets, there are 2 additional requirements:

  • Subnets must not use non-routable address spaces, such as range 192.168.0.0 – 192.168.255.255.
  • There must be routing between the different subnets.

The alternative to fulfilling these additional requirement is to maintain separate Modbus configurations for VaiNet devices in each subnet, and communicate with them separately.

No access to historical data using Modbus

Modbus data integration provides read-only access to latest measurement results and status information. You cannot use it to retrieve historical measurements.