Taking Modbus data integration into use - AP10 - RFL100 - Jade Smart Cloud

Modbus Data Integration with Jade Smart Cloud and VaiNet Technical Note

Product status
Document code
M213335EN-A
ft:locale
en-US
Product
AP10
RFL100
Jade Smart Cloud
Document type
Technical note
  • Your Jade Smart Cloud tenant must have the Modbus data integration add-on license enabled.
  • You must be able to configure the DHCP servers that assign the IP addresses of the AP10 Access Points.
  • You need an Administrator account to the Jade Smart Cloud tenant.
  1. Configure the DHCP server(s) in the subnet(s) that provide AP10 Access Points with IP addresses so that they all receive an unchanging IP address based on their MAC address.

    MAC address of the AP10 is marked below to the Ethernet port, and on the type label of the device

  2. To make sure that the reserved IP addresses are in use, restart every AP10 that is participating in the Modbus data integration.
  3. Create the required Modbus configurations in Jade Smart Cloud. See Creating and editing Modbus configurations in Jade Smart Cloud.
  4. Download the Modbus configuration CSV file(s) from Jade Smart Cloud.
  5. Use the information in the Modbus configuration file(s) and in this document to configure your Modbus client (for example, a BMS system).

    When reading measurement results from RFL100 data loggers, it is important to also check the device status registers:

    • Check that the error code register is not showing any errors.
    • Check the latest measurement time to verify that the measurement is recent. Note that there is also a special case where both measurement values and time are zeroes - this means that the data logger has not sent any measurement data yet.
  6. Test your client to make sure that data is correctly received from the devices.