Modbus registers - AP10 - RFL100 - Jade Smart Cloud

Modbus Data Integration with Jade Smart Cloud and VaiNet Technical Note

Product status
Document code
M213335EN-A
ft:locale
en-US
Product
AP10
RFL100
Jade Smart Cloud
Document type
Technical note

Registers are numbered in decimal, starting from 1. Register addresses in actual Modbus messages (Modbus Protocol Data Unit (PDU)) are in hexadecimal and start from zero. Register number 1 corresponds to address 0x0 in the actual Modbus message.

NOTICE Reading the wrong register(s) may result in correct-looking values. Check the reference documentation of your Modbus host (PLC) to verify which notation it uses for Modbus register addresses.