AP10 Access Point Modbus registers - AP10 - RFL100 - Jade Smart Cloud

Modbus Data Integration with Jade Smart Cloud and VaiNet Technical Note

Product status
Document code
M213335EN-A
ft:locale
en-US
Product
AP10
RFL100
Jade Smart Cloud
Document type
Technical note
AP10 Modbus status data registers (read-only)
Register number Address Description Data format Bitmask / notes
513 0x0200 Error code 16-bit signed integer

0x0000: Status OK

0x0001: Not connected to cloud

0x0002: Not connected to NTP

514 0x0201 Number of connected loggers 16-bit signed integer -
515 0x0202 System time (year) 16-bit signed integer -
AP10 Modbus identification registers (read-only)
Register number Address Description Data format Example contents
7425 0x1D00 Vendor name 8-character ASCII string Constant text: “Vaisala”
7433 0x1D08 Product code 8-character ASCII string “AP10”
7441 0x1D10 Serial number 8-character ASCII string “T1069725”
7449 0x1D18 Software version 8-character ASCII string “1.8.0”
7465 0x1D28 MAC address 8-character ASCII string “28EC9AFB837D”
Test value registers (read-only)
Register number Address Description Data format Value
7937 0x1F00 Signed integer 16-bit integer -12345
7938 0x1F01 Floating point 32-bit float -123.45
7940 0x1F03 Text string 8-character ASCII string "-123.45"