| Code | Name | Reason |
|---|---|---|
| 0x01 | Illegal function | Unsupported function code |
| 0x02 | Illegal data address | Register address or Object ID out of valid ranges |
| 0x03 | Illegal data value | Otherwise invalid request |
| 0x0A | Gateway path unavailable | Requested Unit ID does not exist in the Modbus configuration group |
| 0x0B | Gateway target device failed to respond | Requested Unit ID exists in the Modbus configuration group, but target device is not reachable |
| NOTICE
Requesting measurement data from a data logger that has joined an access point but not sent any measurement data yet will not generate a Modbus exception. Instead, the response will contain a zero value for each requested measurement data register. To distinguish these cases from real zero values, your Modbus client should always read the latest measurement time from the status registers of the data logger. If the time registers also return zero values, the measurement is not a valid zero. |