Function codes - AP10 - RFL100 - Jade Smart Cloud

Modbus Data Integration with Jade Smart Cloud and VaiNet Technical Note

Product status
Document code
M213335EN-A
ft:locale
en-US
Product
AP10
RFL100
Jade Smart Cloud
Document type
Technical note
Modbus function codes
Function code (decimal) Function code (hexadecimal) Name Description
03 0x03 Read Holding Registers

When an AP10 receives a request with this function code, it relays the request to other AP10 devices in the same Modbus configuration group if necessary.

If data from the device with the requested Unit ID cannot be retrieved, the AP10 returns an error.

04 0x04 Read Input Registers When a request with this function code is received by an AP10, it only returns data from itself and data loggers that are directly connected to it. If the device with the requested Unit ID is not connected to the AP10, the AP10 returns an error.