VaiNet device data is read using Modbus through the AP10 devices. Every AP10 device has their own Modbus registers for device information. They also act as a gateway for reading any of the registers from other devices in the same Modbus configuration group.

Reading data requires indicating the target device with an Modbus unit identifier (Unit ID) field. Devices can be accessed with unit identifier values in range 1–255. The unit identifier of each device can be found from the CSV configuration file that you can export from Jade Smart Cloud user interface.

Use Modbus function code 03 (Read Holding Registers) to access data from all devices in the same Modbus configuration group through a single AP10 device.

All multi-register values, such as 32-bit values and multi-character ASCII strings, should be read in a single request as a range of registers.