Configuring analog output - WM80

WM80 User Guide

Document code
M212995EN
Revision
A
ft:locale
en-US
Product
WM80
Document type
User guide

You can configure the analog output over Modbus RTU or by using Vaisala Insight PC software.

Configure the output for wind speed and wind direction separately.

  1. Create a connection to the device with Insight PC software.
  2. Select the settings icon ( ) and Configure device.
  3. Select Analog output, wind speed and configure the following settings.
    Output mode
    Fixed to 4–20 mA.
    Output parameter
    Select sample, instant, or average as the measurement value.
    Scale low end
    The wind speed value 4.0 mA output represents.
    Scale high end
    The wind speed value 20.0 mA output represents.
    Error output level
    Current indicating device failure.
    Output level
    Read-only. The actual (calculated) electrical mA level of the output.
    Test output level
    Set the test output level.
  4. Select Save.
  5. Select Analog output, wind direction and configure the following settings.
    Output mode
    Fixed to 4–20 mA.
    Output parameter
    Select sample, instant, or average as the measurement value.
    Error output level
    Current indicating device failure.
    Output level
    Read-only. The actual (calculated) electrical mA level of the output.
    Test output level
    Set the test output level.