Ingress protection |
- North
America: UL 50E (NEMA) Type 4X or higher
- Rest of the
world: IP65 or higher
|
Flammability rating |
Non-metallic enclosures: According to UL 94: V‑1 or better |
UV resistance (non-metallic enclosures) |
Non-metallic enclosures: According to UL 746C or CSA C22.2 No. 0.17, or both as
appropriate (in North America). The same requirements apply in other
countries. |
Clearance and creepage distances |
Must be maintained between hazardous live parts and accessible parts after installing
the unit with the backplate inside the enclosure. See the following
figure. |
Grounding |
Proper grounding required. Protective bonding must be of low
impedance. |
Ventilation |
Required when there is a battery inside the enclosure |
Heat transfer |
Minimum dimensions
(H × W × D): 600 × 500 × 200 mm (23.62 × 19.69 × 7.78 in)
After
installation, measure the temperature inside the enclosure to
make sure that it stays below the maximum operating temperature
of the weather station. Also, consider the other possible
heat-generating components inside the same enclosure.
|
Access protection |
Key or tool required for opening the enclosure |