You can confgure HART in Insight through
.- Polling address: HART short polling address in which PR53 can be found when polling a HART bus in multidrop mode. It must be unique between devices connected to the same HART bus.
- Configuration change counter: The configuration change counter is incremented once for every change to the device configuration.
- Write protection: Device configuration can be protected by enabling write protection. This disables configuration change using HART.
- Multidrop mode: Disables automatic update of the 4-20 mA analog output channels and sets a fixed value of 4 mA. This is required if multiple HART devices are connected to a single HART bus.
If multidrop mode is activated, the PR53 analog output channel no longer follows the concentration measurement value. |