Outer pipe bend |
- There is sufficient process flow
to the prism that keeps the prism clean.
- When the process is emptied, no
process liquid remains on the prism.
|
|
Vertical pipes |
- There are no excess gas bubbles
or sediments damaging the prism.
- When the process is emptied, no
process liquid remains on the prism.
|
|
Horizontal pipe (pipe side) |
- Use horizontal pipe installation
only if there are no other options.
- Do not install on the top or bottom of the pipe.
|
|
Tank or vessel |
- Install close to a stirrer.
- Do not install to a tank or
vessel with a scraper that touches the tank or vessel walls.
|
|
Feedback control loops |
- Make the lag time short.
- Install close to the dilution
point.
- Make sure the process liquid has mixed properly at the measurement point.
|
|