CAUTION Always switch off the transmitter power supply when connecting or disconnecting screw terminal wiring. Do not energize the transmitter power supply when wiring is not connected. |
CAUTION Always switch the analog output test mode off after testing. Normal analog output is not available in the test output mode. |
- Switch off the transmitter power supply and open the transmitter cover.
- Connect the multimeter wiring to the analog output (1–3) screw terminals and close the transmitter cover.
- Power on the transmitter and connect the transmitter to Insight PC software.
- In the Insight main view, expand the Devices selection on the left panel, select your device and then select the Diagnostics tab.
- In the Diagnostics tab, enter the analog output value you want to send as a test output in the Test output level field. Enter a test value for each analog output separately.
- After entering the test output values, select Save to start sending the entered value as test output.
- Wait for the output to stabilize and then check that the multimeter reading matches the entered test value.
- If the output appears to be incorrect, see Analog output adjustment for information on adjusting the output.
- When you finish testing, clear all values from the Test output level fields and select Save. This stops the test output mode and returns the output back to normal use.
- Switch off the power supply, remove the multimeter wiring and replace the analog output wiring.
- After completing the wiring, close the transmitter cover and switch on the power supply.