This example shows how to use Insight to configure analog output 1 of the transmitter to use the following settings when a humidity and temperature probe is connected to the transmitter:
- 4–20 mA current output
- Relative humidity measurement scaled to 0–100 %RH
- Clipping limit 0 %, error limit 5 %, and error output 3.6 mA
- Connect the transmitter to the Insight software.
- Select and open the Configure device menu.
- Open the General menu and select Current output from the dropdown. Store your selection with Save.
- Return to the Configure device menu and select one of the 3 analog outputs.
- Select 4 ... 20 mA from the Output mode dropdown.
- Select RH from the Output parameter dropdown.
- Type 0 in the Scale low end field.
- Type 100 in the Scale high end field.
- Type 3.6 in the Error output level field.
- Type 0 in the Clipping limit field and 5 in the Error limit field.
- Select Save to take your configuration into use.