Property | Specification |
---|---|
Insight PC software 1 configuration access |
USB-C port on transmitter (compatible with generic USB cables) |
Analog outputs |
3 voltage (V) or current (mA) outputs:
|
Accuracy of analog outputs at +20 °C (+68 °F) | ± 0.1 % full scale |
Relays | 2 configurable relays (V AC/V DC) |
Device maximum specification (resistive load):
|
|
UL-rated maximum specification (resistive load):
|
|
Power supply input 2 |
15 – 30 V DC (24 V AC ±10 % 50/60 Hz) 3 |
Maximum current | Transmitter and connected probe max. 1 A |
Power consumption | Transmitter max. 3 W (+ connected probe, varies depending on probe type) |
Probe connector | M12/5 connector for probe or probe cable connection (Vaisala Indigo-compatible probes) |
Cable lead-throughs | 2 options: rubber lead-through on the bottom of the transmitter, and opening with a seal at the back of the transmitter 4 |
Screw terminal wire size | 0.2 – 1.5 mm2 |
CAUTION Do not modify the unit or use it in ways not described in the documentation. Improper modification or use may lead to safety hazards, equipment damage, failure to perform according to specification, or decreased equipment lifetime. |
1 Vaisala Insight software for
Windows® available at www.vaisala.com/insight.
2 Using a power supply with
overload protection is recommended for electrical safety.
3 When used with the HMP7 probe,
the minimum required power supply input is 18 V DC.
4 Note that the IP65 rating only
applies when the cable gland wiring option is used, and the lead-through with the
pierceable seal at the back of the transmitter is left intact. See Wiring options for more
information.