OPT100 cable glands and connectors - OPT100

OPT100 Quick Guide

Product status
Document code
M212603EN
Revision
C
ft:locale
en-US
Product
OPT100
Document type
User guide
Cable glands and connectors on the bottom of OPT100 cabinet
# Label Description Cable/pipe diameter Tool size Tightening torque
1 Oil Out Oil return to transformer. 10 mm (0.39 in) 19 mm -
2 Oil In Oil intake from transformer. 10 mm (0.39 in) 19 mm -
3 Additional Ground connection. 4–50 mm2 (12–1/0 AWG) conductor 5 mm

3.5 Nm

(4–10 mm2)

10 Nm

(15–50 mm2)
4 RS-485 RS-485 connection. 5–10 mm (0.20–0.39 in) 20 mm 5 Nm
5 Relay control out Relay control to OPTPSU. Use Vaisala cable CBL210539. 7–12 mm (0.28–0.47 in) 24 mm 10 Nm
6 DC in DC input from OPTPSU. Use Vaisala cable CBL210544. 9–16 mm (0.35–0.63 in) 30 mm 12 Nm
7a 1 Ethernet Ethernet connection. Use shielded outdoor Ethernet cable. Assemble the included protection shell on the RJ45 connector. - - -
7b 1 Ethernet Alternative Ethernet connection. Use shielded outdoor Ethernet cable. Assemble the included RJ45 connector. 7–12 mm (0.28–0.47 in) 24 mm 10 Nm
7c Spare Not reserved. Option for Ethernet connection. 5–10 mm (0.20–0.39 in) 20 mm 5 Nm
8 Spare Not reserved. 5–10 mm (0.20–0.39 in) 20 mm 5 Nm
9 Spare Not reserved. 7–12 mm (0.28–0.47 in) 24 mm 10 Nm
1 Cable glands vary for different hardware options