Technical specification - OPT100

OPT100 Quick Guide

Product status
Document code
M212603EN
Revision
C
ft:locale
en-US
Product
OPT100
Document type
User guide
OPT100 measurement specification
Parameter 1 Range Accuracy 2 3 Repeatability 3
Methane (CH4) 0–10 000 ppmv ±4 ppm or ±5 % of reading 10 ppm or 5 % of reading
Ethane (C2H6) 0–10 000 ppmv ±10 ppm or ±5 % of reading 10 ppm or 5 % of reading 4
Ethylene (C2H4) 0–10 000 ppmv ±4 ppm or ±5 % of reading 10 ppm or 5 % of reading
Acetylene (C2H2) 0–5000 ppmv ±0.5 ppm or ±5 % of reading 1 ppm or 5 % of reading
Carbon monoxide (CO) 0–10 000 ppmv ±4 ppm or ±5 % of reading 10 ppm or 5 % of reading
Carbon dioxide (CO2) 0–10 000 ppmv ±4 ppm or ±5 % of reading 10 ppm or 5 % of reading
Hydrogen (H2) 0–5000 ppmv ±15 ppm or ±10 % of reading 15 ppm or 10 % of reading
Moisture 5 (H2O) 0–100 ppmw 6 ±2 ppm 7 or ±10 % of reading Included in accuracy
Oxygen (O2) 8 0–50 000 ppmv ±200 ppm or ±10 % of reading Included in accuracy
Nitrogen (N2) 8 0–150 000 ppmv ±5000 ppm or ±15 % of reading Included in accuracy
Total gas pressure 0–2000 hPa ±10 hPa or ±2 % of reading 10 hPa or 5 % of reading
OPT100 operating environment
Property Description/Value
Transformer liquid type 9 Mineral oil or ester liquids
Required minimum fire point of insulation liquid 10 +125 °C (+257 °F)
Transformer oil pressure at oil inlet

Max. 2 bar (absolute) continuous

Burst pressure 20 bar (absolute)

Transformer insulation liquid temperature at oil inlet

Max. +100 °C (+212 °F)

Min. +0 °C (+32 °F) for ester liquids

Min. temperature for mineral oil depends on the pour point of the mineral oil.

Ambient humidity range 0–100 %RH, condensing
Ambient temperature range in operation −40 … +55 °C (−40 … +131 °F)
Storage temperature range −40 … +60 °C (−40 … +140 °F)

IP rating

IP66: Dust-tight. Protected from powerful water jets from any direction.

OPT100 power supply
Property Description/Value
Operating voltage

OPTPSU1: 100–240 V AC, 50–60 Hz, ±10 %

OPTPSU2: 110–220 V DC, ±10 %

Overvoltage category III
Maximum power consumption 500 W
Typical power consumption at +25 °C (+77 °F) 100 W
Connector

Screw terminals (inside power supply unit)

Wire size 2.5–4 mm2 (14–12 AWG)

OPT100 mechanical specifications
Property Description/Value
Oil fitting

Stainless steel Swagelok® fitting for 10 mm (0.39 in) outer diameter tubing.

See list of available accessories for adapters.

Max. length of oil pipe to transformer for mineral oil

Max. 10 m (33 ft) with 7 mm (0.28 in) inner diameter tubing 11

Max. 5 m (16 ft) with 4 mm (0.15 in) inner diameter tubing

Max. length of pipe to transformer for ester liquid Max. 10 m (33 ft) with 8 mm (0.31 in) inner diameter tubing
Recommended oil pipe properties

10 mm (0.39 in) outer diameter

1–1.5 mm wall thickness (mineral oil devices)

1 mm wall thickness (ester liquid devices)

Material stainless steel

Dimensions (H × W × D)
Installed with ground mounting set and weather shield 1630 × 675 × 453 mm (64 × 27 × 18 in)
Installed with wall mounting set and weather shield 1390 × 675 × 467 mm (55 × 27 × 18 in)
Installed with antivibration wall mounting set and weather shield 1395 × 683 × 541 mm (55 × 27 × 21 in)
Weight
OPT100 DGA Monitor 37 kg (82 lb)
OPTPSU Power Supply Unit 12 kg (27 lb)
OPTMSET1 Wall Mounting Set 8 kg (18 lb)
OPTMSET2 Ground Mounting Set 16 kg (35 lb)
OPTMSET3 Antivibration Wall Mounting Set 9 kg (20 lb)
OPTSHLD1 Weather shield 6 kg (13 lb)
Materials
OPT100 DGA Monitor housing Marine aluminum (EN AW-5754), stainless steel AISI 316
OPTPSU Power Supply Unit housing Stainless steel
OPTMSET1 Wall Mounting Set Stainless steel AISI 316
OPTMSET2 Ground Mounting Set Stainless steel
OPTMSET3 Antivibration Wall Mounting Set Stainless steel
OPTSHLD1 Weather Shield Marine aluminum (EN AW-5754)
Materials in contact with oil
Oil pipes, chambers, and valves Aluminum (EN AW 6026), stainless steel AISI 316, brass
Gaskets and seals NBR, FKM, FVMQ
Pump gears and bushing PEEK/PTFE
1 ppm values are defined as μl/l according to IEC 60567 standard conditions.
2 Accuracy specified is the accuracy of the sensors during calibration gas measurements.
3 Whichever is greater.
4 Repeatability of ethane measurement is specified with averaging of five measurements.
5 Measured as relative saturation (%RS).
6 Upper range limited to saturation.
7 Calculated ppm value is based on average solubility of mineral oils.
8 Optional parameter.
9 Selected when ordering the device.
10 "The fire point [of transformer oil] is normally approximately 10 °C [18 °F] higher than the closed flash point." Heathcote, Martin J. The J & P Transformer Book. 13th ed. Elsevier, 2007.
11 Bigger pipe volume will increase response time.