Duct Installation Kit (Vaisala item ASM214055) is designed to support the probe head of a HMP9 Humidity and Temperature Probe in installations to ducts and chambers. The kit is lightweight and can be installed with minimal tools.

The kit does not include an attachment for the probe body of HMP9. To mount the probe body, use the probe holder supplied with HMP9, or attach it directly to a compatible Indigo transmitter.

Figure 1. Duct Installation Kit ASM214055 dimensions
Figure 2. Duct installation overview
1
Make sure there is a minimum clearance of 5 m (16.5 ft) between the probe head and any possible humidifier. Avoid installing in a location where condensation can fall on the probe head inside the duct.
2
Maximum air flow speed: 50 m/s.
3
Avoid installing the probe in dead legs. Supersaturation can occur in areas where there is no air flow.
4
Install the probe head in a 90° angle to prevent condensation from travelling to the sensor along the mounting pipe. Position the sensor as close to the middle of the duct as possible.