Property | Description/Value |
---|---|
Operating environment |
Outdoor use |
Use in wet location |
Yes |
Operating temperature |
−40 … +55 °C (−40 …+131 °F) 1 |
Operating humidity |
0 … 100 %RH |
Pollution degree |
2 |
Maximum operating altitude |
2000 m (approx. 6500 ft) |
IP rating |
IP65: Dust-tight. Protected from water jets from any direction. |
Property | Description/Value |
---|---|
Input power (AC) |
100 … 240 V AC, ±10 % 50 … 60 Hz 800 mA |
Input power (DC) 23 |
15 … 32 V DC Max. 2 A |
Nominal output voltage, AC input connected |
24 V In backup (battery) mode: 12 V |
Nominal output voltage, AC input not connected | 12 V 4 |
DC output current | Max. 1.2 A |
AC (mains) fuse, internal (non-replaceable) | Type 3, 1.5 kV / 3kA |
AC (mains) cable connection |
|
Overvoltage category | II |
Battery type 5 | Valve-regulated lead-acid (VRLA) battery |
Nominal battery capacity | 12 V DC, 7 Ah |
Expected battery lifetime | 3 … 5 years |
Battery dimensions (H × W × L) | Approx. 97.5 × 65 × 151 mm (3.84 × 2.56 × 5.94 in) |
Property | Description/Value |
---|---|
Dimensions (H × W × L) | 244.5 × 164.2 × 101.0 mm (9.63 × 6.46 × 3.98 in) |
Weight | 4 kg (8.82 lb) |
Material, enclosure | Polycarbonate |
Mating connectors |
|
Test | Standard |
---|---|
EU directives and regulations |
EMC Directive (2014/30/EU) Low Voltage Directive (2014/35/EU) RoHS Directive (2011/65/EU) amended by 2015/863 |
EMC compatibility |
EN 61326‑1, industrial environment CISPR 32 / EN 55032, Class B FCC part 15 B, Class B |
Electrical safety |
EN 61010‑1 |
Cold |
IEC 60068‑2‑1 |
Dry heat |
IEC 60068‑2‑2 |
Vibration |
IEC 60068‑2‑6 IEC 60068‑2‑64 |
Change of temperature |
IEC 60068‑2‑14 |
Damp heat, cyclic |
IEC 60068‑2‑30 |
Rough handling |
IEC 60068‑2‑31 |
Damp heat |
IEC 60068‑2‑78 |
Corrosion and salt mist |
VDA 621‑415 |
Freezing rain | NWS 8.0 |
Compliance marks |
CE, FCC, RCM, UKCA |
- 1
- Phase L
- 2
- Not connected
- 3
- Neutral N
- 4
- Ground PE
- 1
- Power+
- 2
- Not connected
- 3
- GND
- 4
- Not connected
- 1
- Power+
- 2
- RS‑485−
- 3
- GND
- 4
- RS‑485+