This example shows how to configure
analog output channel 1 to use the following settings when a relative humidity probe is
connected to the transmitter as Probe 1:
- 4 … 20 mA current output
- Error output 3.6 mA
- Relative humidity measurement scaled to 0 … 100 %RH
- In the General tab:
- Output mode: 4 … 20 mA
- In the Output 1 tab:
- Output off/on: Set output off to edit settings.
- Parameter: Probe 1, Relative humidity
- Scale low end: 0
- Scale high end: 100
- Error output: 3.6
- Low clipping limit: 3.8
- High clipping limit: 20.5
- Output off/on: Set output on to activate settings.