Analog output configuration example - INDIGO500SERIES - INDIGO510 - INDIGO520

Indigo510, Indigo520 User Guide

Document code
M212287EN
Revision
P
Language
English
Product
INDIGO500SERIES
INDIGO510
INDIGO520
Document type
User guide
This example shows how to configure analog output channel 1 to use the following settings when a relative humidity probe is connected to the transmitter as Probe 1:
  • 4 … 20 mA current output
  • Error output 3.6 mA
  • Relative humidity measurement scaled to 0 … 100 %RH
To configure the analog output, use the following values:
  • In the General tab:
    • Output mode: 4 … 20 mA
  • In the Output 1 tab:
    • Output off/on: Set output off to edit settings.
    • Parameter: Probe 1, Relative humidity
    • Scale low end: 0
    • Scale high end: 100
    • Error output: 3.6
    • Low clipping limit: 3.8
    • High clipping limit: 20.5
    • Output off/on: Set output on to activate settings.