Relay configuration example - INDIGO500SERIES - INDIGO510 - INDIGO520

Indigo510, Indigo520 User Guide

Document code
M212287EN
Revision
P
Language
English
Product
INDIGO500SERIES
INDIGO510
INDIGO520
Document type
User guide
This example shows how to configure a relay to activate when relative humidity measurement from Probe 1 goes above 90 %RH, and to switch off only when the measurement falls below 85 %RH (hysteresis). To configure the relay, use the following values:
  • Relay off/on: Set relay off to edit settings.
  • Parameter: Relative humidity
  • Activation: Active above limit
  • Limit: 90
  • Hysteresis: 5
  • Relay off/on: Set relay on to activate settings.