Measurement data registers - INDIGO500SERIES - INDIGO510 - INDIGO520

Indigo510, Indigo520 User Guide

Document code
M212287EN
Revision
P
Language
English
Product
INDIGO500SERIES
INDIGO510
INDIGO520
Document type
User guide

Measurement data registers in this appendix can be used only for transmitters with optional barometer module and transmitters using analog input, using unit ID 240.

Table 1. Floating point measurement data registers (read-only)
Register number Register address Register description Data format Unit
43 002Ahex Barometric pressure 32-bit float hPa
53 0034hex Actual current level of analog input (mA) 32-bit float mA
55 0036hex Validated current level of analog input (mA) or NaN if analog input is out of valid range (3.8 … 20.5 mA) 32-bit float mA
Table 2. Integer measurement data registers (read-only)
Register number Register address Register description Data format Scale factor Offset Unit
278 0115hex Barometric pressure 16-bit signed integer 10 0 hPa
283 011Ahex Actual level of analog input 16-bit signed integer 1000 0 mA
284 011Bhex Validated level of analog input or 8000hex (-32768) if analog input is out of valid range (3.8 … 20.5 mA) 16-bit signed integer 1000 0 mA