Unit identification of transmitter and probes - INDIGO520 - INDIGO500SERIES - INDIGO510

Indigo510, Indigo520 User Guide

Document code
M212287EN
Revision
M
Language
English (United States)
Product
INDIGO520
INDIGO500SERIES
INDIGO510
Document type
User guide

The transmitter and the connected probes are treated as separate Modbus slaves, each with their own fixed unit identifier (unit ID) value. The unit ID in the Modbus request defines the intended recipient of the request (transmitter or probe).

Table 1. Unit IDs of transmitter and probes
Device Unit ID
Transmitter with barometer module 240
Probe connected to probe 1 connection terminal 241
Probe connected to probe 2 connection terminal 242

The unit IDs of the connected probes identify the probes based on the probe connection terminal that they are connected to. The probes use these unit IDs (241 and 242) only when they are connected to the transmitter. When the probes are accessed directly without the transmitter, the probes have their own Modbus address settings instead of these unit IDs.

If the probe fails to respond to the request, the transmitter responds to the client with the exception code Gateway Target Device Failed to Respond.

For probe-specific register information, see the connected probe's Modbus documentation.