For the AC (mains) power connection, you
need an external disconnecting device (for example, mains power switch).
Note the following:
The disconnecting device must be rated
16 A or 20 A at 250 V AC, and must conform to any additional local regulations.
The disconnecting device must be visible
from the cabinet, or lockable with a key to prevent accidental switching on during
installation and maintenance.
The cabinet must not block access to the
disconnecting device after it has been installed. The disconnecting device must remain
easy to operate.
The AC (mains) cable is not included in the
delivery. Use an AC (mains) cable with a minimum cross-section of
3 × 0.75 mm2 (18 AWG).
Unscrew and remove the transparent cover plate protecting the circuit breaker and the power supply module.
Lead the AC (mains) cable into the enclosure.
Lead the cable through a flange in the cabinet enclosure, following relevant safety regulations. Take note of safe areas around safety
barriers or galvanic isolators inside the enclosure.
Strip approximately 100 mm (4 in) of the cable, and cut the phase and neutral wires to the length of approximately 50 mm (2 in). If you are using a stranded wire, add cable ferrules to
the ends.
CAUTION Make sure that the grounding wire is longer than the phase and neutral wires. Under mechanical stress, the grounding wire
must be the last to disconnect from the protective ground terminal.
Number in figure
Wire
Wire color (international)
Wire color (North America)
Min. … max. wire cross-section
1
Phase L
Brown
Black
Solid wire:
0.75 … 4 mm2 (18 … 12 AWG)
Stranded wire:
0.75 … 2.5 mm2 (18 … 14 AWG)
2
Neutral N
Blue
White
3
Grounding PE/GND
Yellow/Green
Green
Connect the phase, neutral, and grounding wires of the AC (mains) cable as indicated in the figure below.
1
Connect the (green or yellow-green) grounding wire to the grounding terminal block.
2
Connect the phase (L) and neutral (N) wires to the circuit breaker: the phase in the left-hand screw terminal and the neutral in the right-hand screw terminal.
3
Mount the AC (mains) cable to the strain relief fixture located under the circuit breaker.