Operation Pressure Object - HMD60 - HMD65

HMD65 User Guide

Document code
M212243EN
Revision
C
Language
English
Product
HMD60
HMD65
Document type
User guide
Table 1. Operation Pressure Object Properties
Property Data Type Writable Value or Initial Value Persistence
Object_Identifier BACnetObjectIdentifier No

00 80 00 01 (hex)

Object Type = 2,

Instance = 1

Fixed
Object_Name Character String No "OPER P" Fixed
Object_Type BACnet Object Type No 2 (Analog Value) Fixed
Present_Value Real Yes 1013.25 Nonvolatile
Description Character String No "Operation Pressure" Fixed
Units BACnet Engineering Units No 133 (hectopascals) Fixed
Status_Flags BACnet Status Flags No 0 (FAULT == FALSE) Fixed
Event State BACnet Event State No 0 (NORMAL) Fixed
Out_of_Service BOOLEAN No 0 (FALSE) Fixed
Table 2. Status Flags
Flag State Cause
IN_ALARM FALSE Always FALSE
FAULT FALSE Always FALSE)
OVERRIDDEN FALSE Always FALSE
OUT_OF_SERVICE FALSE Always FALSE

Event State

Event State value is always NORMAL.

Out of Service

Out of Service value is not writable.