Property | Data Type | Writable | Value or Initial Value | Persistence |
---|---|---|---|---|
Object_Identifier | BACnetObjectIdentifier | No |
00 80 00 01 (hex) Object Type = 2, Instance = 1 |
Fixed |
Object_Name | Character String | No | "OPER P" | Fixed |
Object_Type | BACnet Object Type | No | 2 (Analog Value) | Fixed |
Present_Value | Real | Yes | 1013.25 | Nonvolatile |
Description | Character String | No | "Operation Pressure" | Fixed |
Units | BACnet Engineering Units | No | 133 (hectopascals) | Fixed |
Status_Flags | BACnet Status Flags | No | 0 (FAULT == FALSE) | Fixed |
Event State | BACnet Event State | No | 0 (NORMAL) | Fixed |
Out_of_Service | BOOLEAN | No | 0 (FALSE) | Fixed |
Flag | State | Cause |
---|---|---|
IN_ALARM | FALSE | Always FALSE |
FAULT | FALSE | Always FALSE) |
OVERRIDDEN | FALSE | Always FALSE |
OUT_OF_SERVICE | FALSE | Always FALSE |
Event State
Event State value is always NORMAL.
Out of Service
Out of Service value is not writable.